Copper Reducing Link 240-120mm²
The CABAC Copper Reducing Link 240-120mm² is designed for creating a permanent crimped connection between 240mm² and 120mm² copper conductors. It is used where different conductor sizes need to be joined while maintaining a strong mechanical connection and reliable electrical continuity.
This reducing link is suitable for circular and sector stranded copper conductors and is commonly used in reducing joints, fly leads, cable tails, switchboard work and general LV power distribution installations. The connector includes an impermeable barrier to help resist the passage of oils and water through the joint.
Key Features
- Suits 240mm² to 120mm² copper conductor reduction
- Suitable for circular and sector stranded copper conductors
- Compression crimp connection
- Suitable for reducing joints, fly leads and cable tails
- Impermeable barrier for oils and water
- Trade-grade CABAC electrical connector
Typical Applications
- LV power cable jointing
- Switchboard and distribution connections
- Cable transition work
- Industrial electrical installations
- Maintenance and cable repairs
Technical Specifications
| Brand |
CABAC |
| Product Type |
Copper reducing link |
| Conductor Size |
240mm² to 120mm² |
| Conductor Material |
Copper |
| Compatible Conductor Form |
Circular and sector stranded copper conductors |
| Installation Method |
Compression crimp |
| Manufacturer Part Number |
CASR240/120 |
Installation Notes
Use suitable crimp tooling and dies for the selected conductor sizes. Confirm conductor preparation, insertion depth and crimp quality before placing the circuit into service.
Product details
Copper Reducing Link
The CABAC copper reducing link range are a barrier type, so they can be used in any situation where an impermeable barrier to oils or water is required.
Note: Do not crimp close to the centre barrier or the links may shear.
Standards and Compliance
AS4325 Part 1 Australia; IEC France; GL/DIN/VDE Germany; JIS Japan; BS United Kingdom; UL/NEMA USA
Technical Data
Nominal Conductor (mm2): 240
Conductive material
Copper 99.95% pure
Oxygen content 30 p.p.m. Max.
Tensile strength 200 MPa
Ductile rating 40%
Final metal state - fully annealed
Operating temperature
-55 to 155 deg C
General electrical properties
Total conductivity 99.7% IACS
Total resistivity 1.738 micro-ohm cm
Plating
This product is not supplied plated since limited shelf life is expected
Dimensional specification
Tooling is interchangeable between Cable Accessories, Utilux and Burndy
Manufacturer specifications
| Cable Size Large End (mm2) |
240 |
| Cable Size Small End (mm2) |
120 |
| Lugs and Links - Material |
Copper |
Product details and specifications from CABAC product data.