Flush-mounted 316L stainless steel enclosure with interlocked switch and socket for clean-area and industrial power connection points.
- Model: PH-SOC-A S316
- Mounting: Flush mounted
- Material: 316L stainless steel
- Brand: Electrix
Product details
Electrix® Flush Mounted Enclosures with Mennekes Interlocked Switches & Sockets, in 316L - V4A - 1.4404 stainless steel, have been designed whilst working closely with project & design engineers from many of the World's leading Pharmaceutical, Food, Brewing and Soft Drinks companies.
Designed to be used where all cabling is conveyed within the cavity of the wall, the main body of the enclosure is recessed meaning that only the lid section and optional components are visible.
This IP66* satin (brushed) finish flush mounted interlocked switch & socket enclosure, is 160 x 280 x 85 (back box H x W x D mm) / 209 x 326 (lid H x W mm).
Complete with an interlocked switch and socket (16 A, 2 Pole + Earth 110 VAC), fixing flange with blue silicone gasket, No. 8 x 40 mm self-tapping screws, DIN rail, gasketed lid, captive lid fixing screws, earth terminals & earth link.
Manufacturer specifications
| Material Type |
Stainless Steel |
| Material Grade |
316L - V4A - 1.4404 |
| Material Finish |
Satin (Brushed) |
| Surface Finish (µm Ra) |
< 0.5 |
| Material Thickness for Lid (mm) |
2.0 |
| Material Thickness for Base (mm) |
1.2 |
| Lid Size (H x W mm) |
209 x 326 |
| Back Box Size (H x W x D mm) |
160 x 280 x 85 |
| Fixing Flange Size (H x W mm) |
200.5 x 320.5 |
| Back Box Height (mm) |
160 |
| Fixing Flange Height (mm) |
200.5 |
| Lid Height (mm) |
209 |
| Back Box Width (mm) |
280 |
| Lid Width (mm) |
326 |
| Fixing Flange Width (mm) |
320.5 |
| Back Box Depth (mm) |
85 |
| Custom Design |
<p>Custom Designs available on request.</p><ul><li>Custom sizes</li><li>Pre-lasered cable entry holes & laser cut apertures</li><li>Extra hygienic lid fixing screws</li><li>Security lid fixing screws</li><li>Additional DIN rails</li><li>Alternative switch handle hole configurations</li></ul><a href="/en-gb/stainless-steel-the-custom-shop/" target="_blank">Click here to visit The Custom Shop.</a> |
| Switched Socket Supplied |
Yes |
| Switched Socket Brand |
Mennekes |
| Voltage (VAC) |
110 |
| Hertz (Hz) |
50-60 |
| Switched Socket (A) |
16 |
| Socket Earth Position |
4h |
| Socket Colour |
Yellow |
| Socket Details |
16 A, 2 Pole & Earth - 110 V |
| Optional Male Plug |
Sold Separately - Part Number: PLUG-A |
| Captive Lid Fixings |
Yes |
| Lift-off Lid / Cover |
Yes |
| Fixing Method |
Supplied with No. 8 x 40 mm self-tapping screws |
| DIN Rail |
Fitted |
| DIN Rail Length (mm) |
260 |
| DIN Rail Style |
35 mm (W) x 7.5 mm (H) - Top Hat |
| DIN Rail Position |
Horizontal / Central |
| Earthing |
Earth terminals & 1 x earth / ground lead* |
| Approvals |
<img alt="NSF" src="/Images/SpecAttributes/spec_logo_NSF.png" style="padding: 2px 10px 5px 0px;"/><img alt="IP66" src="/Images/SpecAttributes/spec_logo_ip66.png" style="padding: 2px 10px 5px 0px;"/><img alt="CE" src="/Images/SpecAttributes/spec_logo_CE_Marking.png" style="padding: 2px 10px 5px 0px;"/>
<img alt="UKCA" src="/Images/SpecAttributes/spec_logo_UKCA_Marking.png" style="padding: 2px 10px 5px 0px;"/> |
| CE Information |
EN 60309-4, EN 60947-3, EN 60947-1, EN 60670-1, EN 60529, EN 63000 |
| Hygiene Standards |
NSF/ANSI/3A 14159-1 Hygiene Requirements for, the Design of Meat and Poultry Processing Equipment |
| International Standards |
IEC 60309 |
| Environmental Rating |
IP66* |
| Pack Quantity |
1 |
| Supplied With |
Interlocked Switch & Socket, Fixing Flange with Blue Silicone Gasket, No. 8 x 40 mm Self-Tapping Screws, DIN Rail, Lid Gasket, Lid Fixings, Earth Terminals & Earth Link |
| Ideally Suited For |
Offshore, Chemical, Food, Dairy, Brewing, Pharmaceutical, Soft Drinks, Architectural companies & many more |
| Alternative Material Finish / Grade |
Polished 316L - V4A - 1.4404 |
| Weight (kg) |
3.37 |
| Fine Print |
*IP rating is only maintained when all apertures are adequately sealed. This is an open enclosure unless suitably rated auxiliary devices are installed to fill the openings., , It is the installer's responsibility to check that the earth / ground lead is suitable for the intended application. |
Specifications from Electrix International product data.