Specifications

Design

Range of product

MAX9

Range

MAX9

Product or component type

surge arrester

Device application

distribution

Warranty

7-year

Physical

Local signalling

flag

[ue] rated operational voltage

240 V +/- 6 % AC 50/60 Hz

Local signalling

white/red flag

Local signalling

flag (white/red)

Mounting mode

clip-on

Mounting support

DIN rail

Height

85 mm

Width

18 mm

Depth

64 mm

Net weight

119 g

Connections - terminals

tunnel type terminal (top or bottom) 2.5-25 mm² rigid|tunnel type terminal (top or bottom) 4-16 mm² flexible

Wire stripping length

14 mm

Standards

IEC 61643-11:2011|EN 61643-11:2012

Ip degree of protection

IP20

Ik degree of protection

IK03 conforming to IEC 62262

Relative humidity

5...95 % at 55 °C

Ambient air temperature for operation

-25...70 °C

Ambient air temperature for storage

-40...85 °C

Reach regulation

Free of Substances of Very High Concern above the threshold

Reach free of svhc

Yes

Eu rohs directive

Compliant

Rohs exemption information

Yes

China rohs regulation

Pro-active China RoHS declaration (out of China RoHS legal scope)

Circularity profile

N/A

Others

Package 1 bare product quantity

1

Poles description

1P

Remote signalling

with

Signal contacts composition

1 NO + 1 NC

Surge arrester type

electrical distribution network

Earthing system

TN-C|TN-S|TT

Surge arrester class type

type 2

Surge arrester technology

MOV

Nominal discharge current

15 kA conforming to IEC 61643-11

Maximum discharge current

40 kA conforming to IEC 61643-11

[uc] maximum continuous operating voltage

350 V AC

Maximum [up] voltage protection level

<1.6 kV type 2

[ures] residual voltage

1545 V

[ut] temporary overvoltage

336 V L/PE 5 s withstand

Signalling circuit voltage

AC: 250 V 50/60 Hz

Signalling output current

0.25 A

Comb busbar and distribution block compatibility

tooth

9 mm pitches

2

Cable cross section

2.5...25 mm² rigid|4...16 mm² flexible

Response time

<= 25 ns

Maximum residual current

0.6 mA 240 V

Tightening torque

3.5...3.5 N.m

Targeted country

Australia

Quality labels

RCM

Pollution degree

2

Operating altitude

0...2000 m

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

7.5 cm

Package 1 width

2.5 cm

Package 1 length

9.5 cm

Package 1 weight

132 g
Show less