Terasaki TemPower 2 AR ACB Body AR2 65kA 2000A 3P with AGR21CL and Shunt Trip
Regular price
£0.00 GBP
Couldn't load pickup availability
Got questions?
Feel free to get in touch.
Price on application. Pricing on this item moves with supplier rates, so we quote it fresh rather than list a price that goes stale.
Email orders@dzelectricalproducts.com for a current price and availability. Quote the SKU shown on this page and we'll come back to you the same business day.
Component Type (ETIM Class)
Power switching circuit breaker
Electrical
Rated current In2000 A
Number of poles3
Max. rated operation voltage Ue AC690 V
Rated ultimate short-circuit breaking capacity lcu at 415 V, 50 Hz65 kA
Rated service short-circuit breaking capacity lcs at 415 V, 50 Hz65 kA
Type of protection trip unitElectronic release
Trip curveLSIG
Frame size rating2000 A
Long time overload protection adjustment range800-2000 A
Instantaneous protection adjustment range4000-32000 A
Integrated earth fault protectionYes
Rated frequency50-60 Hz
Rated insulation voltage Ui1000 V
Suitable for isolationYes
Rated short circuit breaking capacity, Icu 690V AC50 kA
Rated short circuit breaking capacity, Ics 690V AC50 kA
Short time protection adjustment range2000-20000 A
Rated impulse withstand voltage Uimp12 kV
Over voltage categoryIV
Integrated communication functionYes
AC power loss per pole at In164 W
Electrical life at Un, In (service cycles)10000 cycles
Type of electrical connection of main circuitConnection at separate chassis part
Short time withstand current Icw, 1 sec65 kA
Short time withstand current Icw, 3 sec50 kA
Power loss490 W
Communication
Communications protocolModbus RTU
Construction
Air circuit breaker (withdrawable)Yes
Mechanical
Mechanical life (service cycles)12000 cycles
Vibration acceleration (Max)0.7 m/s²
Dimensions
Height490 mm
Width354 mm
Built-in depth385 mm
Weight54 kg
Environment
Pollution degree3
Rated surrounding temperature without derating50 °C
Rated temperature-5-60 °C
Maximum operating temperature60 °C
Allowable relative humidity45-85 %
Altitude before derating (Max)2000 m