Terasaki TemBreak PRO MCCB 250 Frame 25kA 3P 125A Adj. Thermal Adj. Magnetic
Regular price
£0.00 GBP
Couldn't load pickup availability
Got questions?
Feel free to get in touch.
Price on application. Pricing on this item moves with supplier rates, so we quote it fresh rather than list a price that goes stale.
Email orders@dzelectricalproducts.com for a current price and availability. Quote the SKU shown on this page and we'll come back to you the same business day.
Component Type (ETIM Class)
Power switching circuit breaker
Electrical
Rated current In125 A
Number of poles3
Max. rated operation voltage Ue AC525 V
Rated ultimate short-circuit breaking capacity lcu at 415 V, 50 Hz25 kA
Rated service short-circuit breaking capacity lcs at 415 V, 50 Hz19 kA
Type of protection trip unitThermal/magnetic release
Trip curveAdj. thermal, adj. magnetic
Frame size rating250 A
Long time overload protection adjustment range80-125 A
Position of connection for main current circuitFront side
Instantaneous protection adjustment range625-1625 A
Rated frequency50-60 Hz
Rated insulation voltage Ui690 V
Suitable for isolationYes
Rated impulse withstand voltage Uimp8 kV
Over voltage categoryIV
Reverse connection of supply possibleYes
AC power loss per pole at In8.2 W
Electrical life at Un, In (service cycles)6000 cycles
Type of electrical connection of main circuitScrew connection
Power loss24.5 W
Mechanical
DIN rail (top hat rail) mounting optionalYes
Mechanical life (service cycles)18000 cycles
Max. vibration acceleration19 m/s²
Max. vibration frequency, operational16.7 Hz
Max. vibration duration12 min
Dimensions
Cable cross section (range)35-185 mm²
Height165 mm
Width105 mm
Pole connection pitch35 mm
Built-in depth68 mm
Depth (toggle included)95.5 mm
Weight1.5 kg
Environment
Pollution degree3
Rated surrounding temperature without derating50 °C
Rated temperature-5-70 °C
Maximum operating temperature70 °C
Storage temperature-10-70 °C
Allowable relative humidity0-85 %
Max. altitude before derating2000 m
Certificates/Approvals
StandardAS/NZS IEC 60947.2