Product Overview
The CABAC CASR300/240 Copper Reducing Link is a compression connector designed to join a 300mm² copper conductor to a 240mm² copper conductor. It is used where a conductor size reduction is required while maintaining a secure, low-resistance electrical connection.
This reducing link is suitable for circular and sector stranded copper conductors and is commonly used in reducing joints, fly leads, cable tails, switchboards, distribution equipment and heavy-duty electrical installations. Correct tooling and die selection are essential to achieve the intended mechanical and electrical performance.
Key Features
- Connects 300mm² copper conductor to 240mm² copper conductor
- Suitable for circular and sector stranded copper conductors
- Copper construction for high conductivity
- Designed for compression crimp installation
- Suitable for reducing joints, fly leads and tails
- Provides a permanent conductor size transition
Typical Applications
- LV power cable reducing joints
- Switchboard and distribution board connections
- Fly leads and cable tails
- Industrial electrical installations
- Utility and infrastructure cable work
Technical Specifications
| Brand |
CABAC |
| Manufacturer Part Number |
CASR300/240 |
| Product Type |
Copper Reducing Link |
| Large Conductor Size |
300mm² |
| Small Conductor Size |
240mm² |
| Conductor Material |
Copper |
| Compatible Conductor Type |
Circular and sector stranded copper conductors |
| Installation Method |
Compression Crimp |
Installation Notes
Match each conductor to the correct side of the reducing link, fully insert the stripped conductor and crimp using the correct die for each size. Mechanically check the crimp and insulate the finished joint to suit site conditions.
Product details
Copper Reducing Link
The CABAC copper reducing link range are a barrier type, so they can be used in any situation where an impermeable barrier to oils or water is required.
Note: Do not crimp close to the centre barrier or the links may shear.
Standards and Compliance
AS4325 Part 1 Australia; IEC France; GL/DIN/VDE Germany; JIS Japan; BS United Kingdom; UL/NEMA USA
Technical Data
Nominal Conductor (mm2): 300/240
Conductive material
Copper 99.95% pure
Oxygen content 30 p.p.m. Max.
Tensile strength 200 MPa
Ductile rating 40%
Final metal state - fully annealed
Operating temperature
-55 to 155 deg C
General electrical properties
Total conductivity 99.7% IACS
Total resistivity 1.738 micro-ohm cm
Plating
This product is not supplied plated since limited shelf life is expected
Dimensional specification
Tooling is interchangeable between Cable Accessories, Utilux and Burndy
Manufacturer specifications
| Cable Size Large End (mm2) |
300 |
| Cable Size Small End (mm2) |
240 |
| A Dimension (mm) |
105 |
| Lugs and Links - Material |
Copper |
Product details and specifications from CABAC product data.